Executive summary
Date(s) of inspection:
May 2025
Aim of inspection
The aims of this inspection were:
-
To provide regulatory confidence in the implementation of the Hartlepool (HRA) Reactor 1 (R1) Outage Intentions Document in relation to electrical engineering.
-
To provide evidence to inform the ONR decision relating to the issue of a Licence Instrument for a Consent for return to service of Reactor 1 at Hartlepool on completion of the work undertaken during the outage.
An additional aim of this inspection was to provide evidence on station’s compliance against the specific topic area of electrical safety and the requirements of the Electricity at Work Regulations 1989 (E@WR)
Subject(s) of inspection
- LC28 - Examination, inspection, maintenance and testing - Rating: Green
Key findings, inspector's opinions and reasons for judgement made
This was a mid-outage inspection to gain regulatory confidence in the stations implementation of their LC28 arrangements to inform a regulatory decision on whether Hartlepool (HRA) reactor 1 should return to service after its statutory outage (R1/114).
The inspection comprised of discussions, a sample inspection of completed maintenance documentation and a site walkdown with EDF Energy Nuclear Generation Limited (NGL) station representatives at HRA. This focused on progress against EDF’s outage intentions document HAR/OMOA/PD/R1. It included the proactive steps taken to manage leaks and elevated levels on the generator transformer and staff carrying out maintenance of the essential 3.3kV board.
Conclusion
Based on this inspection, I was satisfied that EDF Energy NGL HRA had adequately implemented their LC28 arrangements, I have rated the inspection with a green inspection rating and from an electrical engineering, no issues were identified that would prevent a consent to restart being issued.