Sizewell C - Inspection ID: 54152

Executive summary

Date(s) of inspection

  • July 2026

Aim of inspection

The aim of the inspection is to evaluate SZC Ltd's (referred to as SZC) arrangements in support of delivery, and configuration control, of their pre-construction safety case (PCSR) to provide regulatory confidence in the people and process aspects in advance of ONR's assessment of the PCSR (product) which, along with other evidence, underpin ONR's future permissioning judgement regarding SZC's first nuclear safety concrete (FNSC) activity.

Subject(s) of inspection

  • LC10 - Training - Rating: Green
  • LC14 - Safety documentation - Rating: Green
  • LC17 - Management systems - Rating: Green

Key findings, inspector's opinions and reasons for judgement made

This was a planned compliance inspection seeking confidence in SZC's arrangements in delivery and governance of its pre-construction safety report (PCSR), along with the capability of the personnel delivering it.

In delivering this inspection I sampled the licensee's arrangements, and their implementation, regarding: the PCSR strategy, the PCSR specification, quality control, authoring, peer review, independent verification, independent technical assessment and the identification and control of safety case forward work items, open points and commitments. I also examined the implementation of the licensee's training arrangements to ensure personnel, including contractors, who were involved in delivery of the PCSR are competent to do so.

I found that the licensee has satisfactory arrangements in place providing those delivering the PCSR with adequate context, delivered by the lifetime safety case strategy and the safety case manual. There was a clear PCSR specification and a specification for independent technical assessment. Adequate quality control arrangements were in place, and satisfactorily implemented, and PCSR authoring, review and acceptance was robust, including key aspects of the barrier model delivered by independent technical assurance and the nuclear safety committee. I found that PCSR configuration control is maintained, as is the management of future work items/safety case open points/safety case commitments, with adequate gradings based upon risk. Training of personnel is satisfactory to provide confidence that only suitably qualified and experienced persons (SQEP) are used in delivery of the PCSR.

I have rated each of the three licence conditions (LC 10, LC 12 and LC 14) as green as, based upon my sampling, SZC has demonstrated adequate compliance with the expectations of those licence conditions.

Conclusion

From my sampling of SZC's arrangements, and their implementation, in delivery of their pre-construction safety report (PCSR) my judgement is:

LC 14

I judge that an inspection rating of GREEN (no formal action) is appropriate for LC 14: safety documentation.

The focus of the LC 14 aspects of the inspection included, for example, how SZC specifies the format, content and purpose and each safety document, that adequate peer review and independent assessment takes place, that arrangements are graded to the significance of the hazard, that suitably qualified experienced persons (SQEPs) are used.

Sampling SZC's arrangements and their implementation confirmed SZC was compliant with the expectations of LC 14 - personnel responsible for authoring, review or acceptance of the PCSR had, and implemented, adequate guidance supporting an understanding of why, what and how to satisfactorily deliver the PCSR.

LC 17

I judge that an inspection rating of GREEN (no formal action) is appropriate for LC 17: management systems.

The focus of the LC 17 aspects of the inspection included, for example, governance, internal regulation in the demonstration that effective processes were being implemented.

Sampling SZC's arrangements and their implementation confirmed SZC was compliant with the expectations of LC 17 - adequate governance was demonstrated in the delivery of PCSR along with evidence of robust internal regulation.

LC 10

I judge that an inspection rating of GREEN (no formal action) is appropriate for LC 10: training.

The focus of the LC 10 aspects of the inspection included, for example, confirmation that competent individuals were used in PCSR delivery, that their competence was up to date, the competence was applicable to their role and individuals still in training had adequate mentorship so as to maintain safety.

Sampling SZC's arrangements and their implementation confirmed SZC was compliant with the expectations of LC 10 - competent personnel was used in PCSR delivery, their competence was up to date and applicable to their role and adequate mentorship was provided in the interests of safety.