Office for Nuclear Regulation

Site inspection to ensure compliance with the Regulatory Reform (Fire Safety) Order 2005

Executive summary

Purpose of Intervention

This was a planned inspection at Dungeness B Nuclear Power Station, undertaken as part of the intervention strategy for Operating Facilities Division.

The purpose of the intervention was to ensure that the Licensee was demonstrating compliance with the requirements of the Regulatory Reform (Fire Safety) Order 2005 to ensure the safety of people from the danger of fire.

Interventions carried out by ONR

This intervention was a planned remote Compliance Inspection undertaken against the life safety requirements of the Regulatory Reform (Fire Safety) Order 2005.

The intervention was completed remotely due to COVID-19 restrictions. ONR could not therefore directly inspect the implementation of fire safety management procedures or assess directly the effectiveness of the activities being undertaken on the site or independently confirm actual compliance with Company processes.

Explanation of Judgement if Safety System Not judged to be Adequate

Not Applicable

Key Findings, Inspector's Opinions and Reasons for Judgements Made

The Fire Coordinator described that there had been a lot of work to maintain fire safety management standards as a consequence of Covid-19 precautions. There were a number of areas of industry good practice explained during the intervention, including:

Progress on the following items, identified during the last site inspection, has been good and not adversely affected by virus precautions;

I did not identify any significant departures from compliance that will require follow up as part of regulatory interactions. No matters were identified as requiring immediate regulatory attention during the course of the compliance intervention.

Conclusion of Intervention

I concluded that the sampled areas of fire safety arrangements, within the limitations of remote inspection, are compliant with the legislation and that there are a number of examples of best practice.

I have rated the outcome of this inspection as GREEN.